4 Serial RS485 defaults into the Type field. When
establishing a PRO-2200 panel loop, RS485 is
the only type applicable.
5 Select the Port to which the loop is connected.
6 The communication rate for the loop is indicated
in the Bits per Second field. This field defaults
to 38400 but can be set at 9600 or 19200 as well
when using RS-485 communication.
NOTE: An RS-232 to RS-485 converter is required
(Part # PRO22CVT1).
7 IC Reply Timeout is the duration the Host PC
(DLL) will wait for an acknowledgment after it
has sent an outgoing packet. If acknowledgment
is not received within the specified time, the
Host PC (DLL) will re-send the packet. The host
will retry according to the Host Retry Count set
in the panel.
3 Click the Next button to advance to the Port
Settings window (next illustration).
NOTE: An ADV cannot be created for the PRO-2200
panel loop.
Loop PRO-2200 Configuration - Port Settings